top of page
LV429037

LV429037

SKU: 101
$55.00Price

LV429037-SCHNEIDER

trip unit TM16D for ComPact NSX 100 circuit breakers, thermal magnetic, rating 16 A, 3 poles 3d

In Stock

This TM16D is a 3 poles 3d thermal-magnetic trip unit used on Compact NSX 100 circuit breakers. This 16A rating thermal-magnetic trip unit is an optimum choice for all distribution applications. It embeds an adjustable thermal overload protection and a fixed magnetic protection against short-circuits. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.

 

  • Addisional Information

    Complementary
    Long-time pick-up adjustment type Ir (thermal protection) Adjustable
    [Ir] long-time protection pick-up adjustment range 0.7...1 x In
    Long-time protection delay adjustment type tr Fixed
    [tr] long-time protection delay adjustment range 120…400 s at 1.5 x In
    15 s at 6 x Ir
    Short-time protection pick-up adjustment type Isd Fixed
    [Isd] Short-time protection pick-up adjustment range 190 A
    Short-time protection delay adjustment type tsd Fixed
    earth-leakage protection Without
No Reviews YetShare your thoughts. Be the first to leave a review.