G20B3A63
G20B3A63 - SCHNEIDER
Circuit breaker, GoPact MCCB 200, 3 poles, 25kA at 415VAC, 63A rating, TMD trip unit, adjustable thermal protection
IN STOCK
Description
This product is part of the new GoPact Molded Case Circuit Breakers range (MCCB). It is a complete 3 poles circuit breaker made of a 200A breaker frame and of a thermal magnetic trip unit (TMD). GoPact MCCB has a good price-performance ratio for basic applications and delivers a reliable electrical protection for your applications. The breaking capacity (Icu) is 25kA rms at 415VAC 50/60Hz. The operational voltage is 415VAC 50/60Hz. This product embeds a 63A rating (In) thermal-magnetic trip unit (TMD). This TMD trip unit provides an adjustable thermal protection Ir (against overloads) with a setting range from 0.7xIn to 1xIn (44.1A-63A). And it provides a fixed magnetic (against short-circuits) protection set to 12xIn (756A). GoPact MCCB comes with a variety of optional accessories simple to choose and to install. Product dimensions are 75mm (Width) x 130mm (Height) x 60mm (Depth). The weight is 0.9 kg. GoPact MCCB 200 is IEC 60947-1 and IEC 60947-2 certified. GoPact MCCB range benefits from Schneider Electric quality assurance.
Product code / GTIN :G20B3A63
Specifications
Main Range of product GoPact MCCB product or component type Circuit breaker Product name GoPact MCCB 200 Device application Distribution poles description 3P Protected poles description 3D [In] rated current 63 A at 40 °C [Ue] rated operational voltage 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 Suitability for isolation Yes conforming to EN/IEC 60947-2 Utilisation category Category A [Icu] rated ultimate short-circuit breaking capacity 25 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2Performance level B 25 kA 380/415 V AC Trip unit name TM-D Trip unit technology Thermal-magnetic Trip unit protection functions LI Control type Toggle Circuit breaker mounting mode Fixed Complementary [Ui] rated insulation voltage 440 V AC conforming to EN/IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2 [Ics] rated service short-circuit breaking capacity 25 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2Mechanical durability 30000 cycles Electrical durability 8000 cycles at 415 V In Power dissipation per pole 16 W mounting support Backplate Mounting position Horizontal and vertical
Flat on the backUpside connection Front downside connection Front Connection terminals Screw terminals Connection pitch 25 mm Protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)Trip unit rating 63 A at 40 °C Long-time pick-up adjustment type Ir (thermal protection) Adjustable [Ir] long-time protection pick-up adjustment range 0.7...1 x In Long-time protection delay adjustment type tr Fixed Instantaneous protection pick-up adjustment type Ii Fixed [Ii] instantaneous protection pick-up adjustment range 12 x In Width (W) 75 mm Height (H) 130 mm Depth (D) 60 mm net weight 0.9 kg Colour Grey (RAL 7035) Environment Standards EN/IEC 60947-1
EN/IEC 60947-2
EN/IEC 60947-2 Annex HOvervoltage category III Pollution degree 3 conforming to IEC 60664-1 IP degree of protection IP20 conforming to IEC 60529 Ambient air temperature for operation -20…55 °C ambient air temperature for storage -35…85 °C Operating altitude 0...2000 m without derating
2000...5000 m with derating