A9F73125
A9F73125 - scheinder
Miniature circuit-breaker, Acti9 iC60N, 1P, 25 A, B curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)
stock : 27
Description
This Acti9 iC60N is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 25A rated current and B tripping curve. The rated short circuit breaking capacity goes up to 10kA at 220VAC to 240VAC conforming to EN/IEC 60947-2 standard and 6000A at 230VAC conforming to EN/IEC 60898-1 standard. It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker protects circuits against short circuit and overload current. Its unique VisiTrip indicator reduces intervention time by showing the faulty circuit. Its VisiSafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ui rated insulation voltage is 500VAC. Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is white (RAL9003). The dimensions are (W) 18mm x (H) 85mm x (D) 78.5mm. The weight is 0.215kg. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is -35°C to 70°C. The storage temperature is -40°C to 85°C.
properties
iC60N - miniature circuit breaker - 1P - 25A - B curve
Date : 13/08/2023Type : Declaration of ConformityLanguages : TurkishVersion :Reference : A9F73125_ROHS_DECLARATIONCompliance Information: EU RoHS StatementCountry: InternationalEnvironment: GeneralMiniature circuit-breaker, Acti9 iC60N, 1P, 25 A, B curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)
A9F73125
To be discontinued on:1 Dec 2024
Poles description:1P
[In] rated current:25 A
Curve code:B
Specifications Main
Main Device application Distribution Range Acti9 Product name Acti9 iC60 Product or component type Miniature circuit-breaker Device short name IC60N Poles description 1P Number of protected poles 1 [In] rated current 25 A Network type DC
ACTrip unit technology Thermal-magnetic Curve code B Breaking capacity 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2
15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2
10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2Utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2Suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2Standards EN 60898-1
IEC 60898-1
IEC 60947-2
EN 60947-2Complementary Network frequency 50/60 Hz Magnetic tripping limit 4 x In +/- 20 % [Ics] rated service breaking capacity 27 kA 75 % conforming to EN 60947-2 - 12...60 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 - 100...133 V AC 50/60 Hz
15 kA 75 % conforming to EN 60947-2 - 100...133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 - 230 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 - 230 V AC 50/60 Hz
10 kA 100 % conforming to EN 60947-2 - 72 V DC
10 kA 100 % conforming to IEC 60947-2 - 72 V DC
15 kA 100 % conforming to EN 60947-2 - 12...60 V DC
15 kA 100 % conforming to IEC 60947-2 - 12...60 V DCLimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2Contact position indicator Yes Control type Toggle Local signalling Trip indicator Mounting mode Fixed Mounting support DIN rail Comb busbar and distribution block compatibility Top or bottom: YES 9 mm pitches 2 Height 85 mm Width 18 mm Depth 78.5 mm Net weight 0.215 kg Colour White Mechanical durability 20000 cycles Electrical durability 10000 cycles Connections - terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexibleWire stripping length 14 mm for top or bottom connection Tightening torque 2 N.m top or bottom Earth-leakage protection Without Environment and Packing Units
Environment IP degree of protection IP20 conforming to IEC 60529
IP20 conforming to EN 60529Pollution degree 3 conforming to EN 60947-2
3 conforming to IEC 60947-2Overvoltage category IV Tropicalisation 2 conforming to IEC 60068-1 Relative humidity 95 % at 55 °C Operating altitude 0...2000 m Ambient air temperature for operation -35…70 °C Ambient air temperature for storage -40…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 7.5 cm Package 1 Width 1.8 cm Package 1 Length 9.5 cm Package 1 Weight 115.0 g Unit Type of Package 2 BB1 Number of Units in Package 2 12 Package 2 Height 8.0 cm Package 2 Width 9.8 cm Package 2 Length 22.5 cm Package 2 Weight 1.45 kg Unit Type of Package 3 S03 Number of Units in Package 3 132 Package 3 Height 30.0 cm Package 3 Width 30.0 cm Package 3 Length 40.0 cm Package 3 Weight 16.428 kg