A9F44110
A9F44110 - SCHNEIDER
Miniature circuit breaker (MCB), Acti9, iC60N Disbo, 1P, 10A, C curve, 6000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)
stock : 500
Description
This Acti9 iC60N is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 10A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 220VAC to 240VAC conforming to EN/IEC 60947-2 standard and 6000A at 240VAC conforming to EN/IEC 60898-1 standard. It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker protects circuits against short circuit and overload current. Its unique VisiTrip indicator reduces intervention time by showing the faulty circuit. Its VisiSafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ui rated insulation voltage is 500VAC. Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. The product colour is white (RAL9003). The dimensions are (W) 18mm x (H) 85mm x (D) 78.5mm. The weight is 0.125kg. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is -35°C to 70°C. The storage temperature is -40°C to 85°C.
Specifications Main
Main Range Acti9 Product name Disbo iC60 Product or component type Miniature circuit-breaker Device short name IC60N poles description 1P Number of protected poles 1 [In] rated current 10 A network type AC Trip unit technology Thermal-magnetic Curve code C Breaking capacity 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2
10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2
6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 10...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2Utilisation category Category A conforming to EN/IEC 60947-2 Complement
network frequency 50/60 Hz [Ue] rated operational voltage 240 V AC 50/60 Hz Magnetic tripping limit 8 x In +/- 20 % [Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 - 10...60 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 - 240 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 - 12...48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 - 72 V DCLimitation class 3 conforming to EN/IEC 60947-2 [Ui] rated insulation voltage 500 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2 Contact position indicator Yes Control type Toggle local signalling Trip indicator mounting mode Clip-on mounting support Rail 9 mm pitches 2 Height 85 mm Width 18 mm Depth 78.5 mm Net weight 0.125 kg Colour White Mechanical durability 20000 cycles Electrical durability 10000 cycles Provision for padlocking Padlockable Connections - terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexibleWire stripping length 14 mm for top or bottom connection Tightening torque 2 N.m top or bottom Earth-leakage protection Separate block Environment $Packing Units
Environment Standards EN/IEC 60898-1
EN/IEC 60947-2IP degree of protection IP20 conforming to IEC 60529 Pollution degree 3 conforming to EN/IEC 60947-2 Tropicalisation 2 conforming to IEC 60068-1 Relative humidity 95 % at 55 °C Ambient air temperature for operation -35…70 °C Ambient air temperature for storage -40…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 7.500 cm Package 1 Width 1.800 cm Package 1 Length 9.500 cm Package 1 Weight 108.000 g Unit Type of Package 2 BB1 Number of Units in Package 2 12 Package 2 Height 8.500 cm Package 2 Width 9.800 cm Package 2 Length 22.000 cm Package 2 Weight 1.356 kg Unit Type of Package 3 S03 Number of Units in Package 3 132 Package 3 Height 30.000 cm Package 3 Width 30.000 cm Package 3 Length 40.000 cm Package 3 Weight 15.200 kg Properties
- Suitability for industrial isolation according to IEC/EN 60947-2 standard
- Combine short-circuit and overload currents protection
- VisiTrip system for fast detection of faulty outgoers for shorter repair times
- VisiSafe system for offering enhanced security when it comes to circuit protection
- Option to add auxiliaries, remote monitoring and residual current device (Vigi)
- Environmental performance of the product Learn more