2CDS273001R0404
2CDS273001R0404 - ABB
S203M-C40 Miniature Circuit Breaker - 3P - C - 40 A
In Stock
Description:
System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.
Dimensions
Width in Number of Modular Spacings: 3
Product Net Width: 52.5 mm
Product Net Height: 88 mm
Product Net Depth / Length: 69 mm
Product Net Weight: 0.375 kg
Pole Net Weight: 0.125 kg
Built-In Depth (t2): 69 mm
Dimension Diagram:
2CDC022007F0010
Environmental
Ambient Air Temperature:
Operation -25 ... +55 °C
Storage -40 ... +70 °C
Reference Ambient Air Temperature: 30 °C
Degree of Protection:
IP20
IP40
Enclosure with Cover IP40
Pollution Degree: 3
Environmental Conditions:
28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Resistance to Vibrations:
20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz
Resistance to Shock acc. to IEC 60068-2-27:
25g 2 shocks 13 ms
Technical
Standards:
IEC/EN 60898-1
CSA 22.2 No. 235
IEC/EN 60947-2
UL 1077
Tripping Characteristic: C
Rated Operational Voltage:
acc. to IEC 60898-1 400 V AC
acc. to IEC 60898-1 400 V
acc. to IEC 60947-2 440 V AC
Operational Voltage:
Maximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC
Minimum 12 V DC
Rated Insulation Voltage (Ui):
acc. to IEC/EN 60664-1 440 V
Rated Impulse Withstand Voltage (Uimp):
4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
Dielectric Test Voltage:
50/60 Hz, 1 min: 2 kV
Input Voltage Type: AC/DC
Rated Current (In): 40 A
Rated Short-Circuit Capacity:
(AC) 10 kA
(230 V AC) 10 kA
(400 V AC) 10 kA
(400 V) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(230 V AC) 25 kA
(400 V AC) 15 kA
(440 V AC) 15 kA
(230 V) 25 kA
(400 V) 15 kA
Rated Conditional Short-Circuit Current (Inc):
(230 V) 15 kA
(400 V) 25 kA
Rated Service Short-Circuit Breaking Capacity (Ics):
(230 V AC) 7.5 kA
Frequency (f): 50 Hz
Rated Frequency (f): 50 / 60 Hz
Power Loss: 14.4 W
at Rated Operating Conditions per Pole 4.8 W
Power Supply Connection: Arbitrary
Contact Position Indication:
Red ON / Green OFF
Energy Limiting Class: 3
Electrical Endurance: 10000 AC cycle
Mechanical Endurance: 20000 cycle
Number of Protected Poles: 3
Number of Poles: 3