2904621
2904621 - phoenix
QUINT4-PS/3AC/24DC/10 - Power supply unit QUINT4-PS/3AC/24DC/10 - Power supply unit 2904621
in stock: available
description
Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, and NFC interface, input: 3-phase, output: 24 V DC/10 A
Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, and NFC interface, input: 3-phase, output: 24 V DC/10 A
The fourth generation of the high-performance QUINT POWER power supplies ensures superior system availability by means of new functions. Signaling thresholds and characteristic curves can be individually adjusted via the NFC interface.
The unique SFB technology and preventive function monitoring of the QUINT POWER power supply increase the availability of your application.
input data
Control input (configurable) Rem Output power ON/OFF (SLEEP MODE) Default Output power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd) AC operation Network type Star network Nominal input voltage range 3x 400 V AC ... 500 V AC 2x 400 V AC ... 500 V AC Input voltage range 3x 400 V AC ... 500 V AC -20 % ... +10 % 2x 400 V AC ... 500 V AC -10 % ... +10 % Typical national grid voltage 400 V AC 480 V AC Voltage type of supply voltage AC Inrush current typ. 3 A (at 25 °C) Inrush current integral (I2t) < 0.1 A2s Inrush current limitation 3 A (after 1 ms) AC frequency range 50 Hz ... 60 Hz -10 % ... +10 % Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 % Mains buffering time typ. 29 ms (3x 400 V AC) typ. 26 ms (3x 480 V AC) Current consumption 3x 0.5 A (400 V AC) 3x 0.41 A (480 V AC) 2x 1.1 A (400 V AC) 2x 0.91 A (480 V AC) 3x 0.4 A (500 V AC) 2x 1.1 A (500 V AC) Nominal power consumption 274 VA Protective circuit Transient surge protection; Varistor, gas-filled surge arrester Power factor (cos phi) 0.91 Switch-on time < 1 s Typical response time 300 ms (from SLEEP MODE) Recommended breaker for input protection 3x 4 A ... 20 A (Characteristic B, C or comparable) Recommended fuse for input protection ≥ 300 V AC Discharge current to PE < 3.5 mA 1 mA (550 V AC, 60 Hz) DC operation Nominal input voltage range ± 260 V DC ... 300 V DC Input voltage range ± 260 V DC ... 300 V DC -13 % ... +30 % Voltage type of supply voltage DC Current consumption 0.7 A (± 260 V DC) 0.6 A (±300 V DC) Recommended breaker for input protection 1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms) Recommended fuse for input protection ≥ 1000 V DC output data
Efficiency typ. 93 % (400 V AC) typ. 92.6 % (480 V AC) Output characteristic U/I Advanced Smart HICCUP FUSE MODE Nominal output voltage 24 V DC Setting range of the output voltage (USet) 24 V DC ... 29.5 V DC (constant capacity) Nominal output current (IN) 10 A Static Boost (IStat.Boost) 12.5 A Dynamic Boost (IDyn.Boost) 20 A (5 s) Selective Fuse Breaking (ISFB) 60 A (15 ms) Magnetic circuit breaker tripping A1...A6 / B2...B6 / C1...C3 / Z1...Z6 Derating > 60 °C ... 70 °C (2.5 %/K) Feedback voltage resistance ≤ 35 V DC Protection against overvoltage at the output (OVP) ≤ 32 V DC Control deviation < 0.5 % (Static load change 10 % ... 90 %) < 2 % (Dynamic load change 10 % ... 90 %, (10 Hz)) < 0.25 % (change in input voltage ±10 %) Residual ripple < 75 mVPP (with nominal values) Short-circuit-proof yes No-load proof yes Output power 240 W 300 W 480 W Apparent power 346 VA (400 V, UOUT = 24 V, IOUT = stat. Boost) 349 VA (480 V, UOUT = 24 V, IOUT = stat. Boost) Maximum no-load power dissipation < 5 W (400 V AC) < 5 W (480 V AC) Power loss nominal load max. < 19 W (400 V AC) < 20 W (480 V AC) Power dissipation SLEEP MODE < 5 W (400 V AC) < 5 W (480 V AC) Crest factor typ. 1.8 (400 V AC) typ. 2.25 (480 V AC) Rise time < 1 s (UOut = 10 % ... 90 %) Connection in parallel yes, for redundancy and increased capacity Connection in series yes Signal Signal ground SGnd Reference potential for Out1, Out2, and Rem Signal Out 1 (configurable) Digital 24 V DC 20 mA Default 24 V DC 20 mA 24 V DC for UOut > 0.9 x USet Signal Out 2 (configurable) Digital 24 V DC 20 mA Analog 4 mA ... 20 mA ±5 % (Load ≤400 Ω) Default 24 V DC 20 mA 24 V DC for POut < PN Signal relay 13/14 (configurable) Default closed (Uout > 0.9 USet) Digital 24 V DC 1 A 30 V AC/DC 0.5 A connection data
Input Connection method Screw connection Conductor cross section, rigid min. 0.2 mm² Conductor cross section, rigid max. 6 mm² Conductor cross section flexible min. 0.2 mm² Conductor cross section flexible max. 4 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min. 0.25 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max. 4 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min. 0.25 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max. 4 mm² Conductor cross section AWG min. 24 Conductor cross section AWG max. 10 Stripping length 8 mm Tightening torque, min 0.5 Nm Tightening torque max 0.6 Nm Output Connection method Screw connection Conductor cross section, rigid min. 0.2 mm² Conductor cross section, rigid max. 2.5 mm² Conductor cross section flexible min. 0.2 mm² Conductor cross section flexible max. 2.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min. 0.25 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max. 2.5 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min. 0.25 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max. 2.5 mm² Conductor cross section AWG min. 24 Conductor cross section AWG max. 14 Stripping length 6.5 mm Tightening torque, min 0.5 Nm Tightening torque max 0.6 Nm Properties
mouting
Mounting type DIN rail mounting Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottomMounting position horizontal DIN rail NS 35, EN 60715 With protective coating No electrical data
Number of phases 3.00 Insulation voltage input/output 4 kV AC (type test) 2.4 kV AC (routine test) Insulation voltage output / PE 0.5 kV DC (type test) 0.5 kV DC (routine test) Insulation voltage input / PE 3.5 kV AC (type test) 2.4 kV AC (routine test) Switching frequency 90.00 kHz ... 110.00 kHz (Auxiliary converter stage) 56.00 kHz ... 500.00 kHz (Main converter stage) 25.00 kHz ... 500.00 kHz (PFC stage)
Properties product
Product type Power supply Product family QUINT POWER MTBF (IEC 61709, SN 29500) > 1034000 h (25 °C) > 654000 h (40 °C) > 320000 h (60 °C) Environmental protection directive RoHS Directive 2011/65/EU WEEE Reach Insulation characteristics Protection class I Degree of pollution 2 Life expectancy (electrolytic capacitors) Current 5 A Temperature 40 °C Time 389000 h Additional text 400 V AC Life expectancy (electrolytic capacitors) Current 5 A Temperature 40 °C Time 364000 h Additional text 480 V AC Life expectancy (electrolytic capacitors) Current 10 A Temperature 25 °C Time 566000 h Additional text 400 V AC Life expectancy (electrolytic capacitors) Current 10 A Temperature 25 °C Time 520000 h Additional text 480 V AC Life expectancy (electrolytic capacitors) Current 10 A Temperature 40 °C Time 200000 h Additional text 400 V AC Life expectancy (electrolytic capacitors) Current 10 A Temperature 40 °C Time 183000 h Additional text 480 V AC