top of page
1SFL467001R1311

1SFL467001R1311

SKU: TR
$215.15Price

AF146-30-11-13

General Information

  • Extended Product Type:

    AF146-30-11-13

  • Product ID:

    1SFL467001R1311

  • EAN:

    7320500476994

  • Catalog Description:

    AF146-30-11-13 Contactor

  • Long Description:

    The AF146-30-11-13 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and double clamp, controlling motors up to 75 kW / 400 V AC (AC-3) or 100 hp / 480 V UL and switching power circuits up to 225 A (AC-1) or 200 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.

  • Popular Downloads

  • Data Sheet, Technical Information:

    1SBC100192C0206

  • Instructions and Manuals:

    1SFC100003M0201

  • CAD Dimensional Drawing:

    2CDC001079B0201

  • Dimension Diagram:

    1SFB535001G1051

  • Dimensions

  • Product Net Width:

    90 mm

  • Product Net Depth / Length:

    126 mm

  • Product Net Height:

    150 mm

  • Product Net Weight:

    1.55 kg

  • Technical

  • Number of Main Contacts NO:

    3

  • Number of Main Contacts NC:

    0

  • Number of Auxiliary Contacts NO:

    1

  • Number of Auxiliary Contacts NC:

    1

  • Rated Operational Voltage:

    Main Circuit 1000 V

  • Rated Frequency (f):

    Main Circuit 50 / 60 Hz

  • Conventional Free-air Thermal Current (Ith):

    acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 225 A

  • Rated Operational Current AC-1 (Ie):

    (1000 V) 40 °C 225 A
    (1000 V) 55 °C 200 A
    (1000 V) 60 °C 200 A
    (1000 V) 70 °C 175 A
    (690 V) 40 °C 225 A
    (690 V) 55 °C 200 A
    (690 V) 60 °C 200 A
    (690 V) 70 °C 175 A

  • Rated Operational Current AC-3 (Ie):

    (415 V) 55 °C 146 A
    (440 V) 55 °C 146 A
    (500 V) 55 °C 130 A
    (690 V) 55 °C 93 A
    (1000 V) 55 °C 60 A
    (380 / 400 V) 55 °C 146 A
    (220 / 230 / 240 V) 55 °C 146

  • Rated Operational Current AC-3e (Ie):

    (415 V) 60 °C 146 A
    (440 V) 60 °C 146 A
    (500 V) 60 °C 130 A
    (690 V) 60 °C 93 A
    (1000 V) 60 °C 54 A
    (380 / 400 V) 60 °C 146 A
    (220 / 230 / 240 V) 60 °C 146 A

  • Rated Operational Power AC-3 (Pe):

    (415 V) 75 kW
    (440 V) 90 kW
    (500 V) 90 kW
    (690 V) 90 kW
    (1000 V) 75 kW
    (380 / 400 V) 75 kW
    (220 / 230 / 240 V) 45 kW

  • Rated Operational Power AC-3e (Pe):

    (415 V) 75 kW
    (440 V) 90 kW
    (500 V) 90 kW
    (690 V) 90 kW
    (1000 V) 75 kW
    (380 / 400 V) 75 kW
    (220 / 230 / 240 V) 45 kW

  • Rated Breaking Capacity AC-3:

    8 x Ie AC-3

  • Rated Breaking Capacity AC-3e:

    8.5 x Ie AC-3e

  • Rated Making Capacity AC-3:

    10 x Ie AC-3

  • Rated Making Capacity AC-3e:

    12 x Ie AC-3e

  • Short-Circuit Protective Devices:

    gG Type Fuses 315 A

  • Rated Short-time Withstand Current Low Voltage (Icw):

    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A

  • Maximum Breaking Capacity:

    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1500 A

  • Maximum Electrical Switching Frequency:

    (AC-1) 300 cycles per hour
    (AC-2 / AC-4) 150 cycles per hour
    (AC-3) 300 cycles per hour

No Reviews YetShare your thoughts. Be the first to leave a review.

Relpol 